RS485 Communication for VPFlowScope M

RS485 Communication for VPFlowScope M

RS485 Communication

 

Real time value of Temperature in Celsius (204-205)

 

[RTU]  Tx:     09  03  00  CC  00  02  05  7C

 

Slave Address: 09

Function Code: 03

Starting Address: 00 CC

Quantity of Registers: 00 02

CRC: 05 7C

 

[RTU]    Rx:     09  03  04  1C  20  41  CD  84  6C

 

Slave Address: 09

Function Code: 03

Byte Count: 04

Register Values: 1C  20  41  CD 

CRC: 84  6C

 

Data format:

Function code 0x03 for reading(Holding register)

Function code 0x10 for writing (Holding register)

32-bit Floating point Little endian [CDAB]

32-bit signed Integer Little endian [CDAB]

    • Related Articles

    • VPFlowScope M shows no Flow.

      There can be two reasons for this: 1. If you have recently updated or going to update your VPFlowScope M to the latest firmware (2.2.0), please be careful about the diameter. The diameter of the transmitter will be set to 0 after a firmware update. ...
    • USB Isolator for connection to VPStudio

      The VPFlowScope M can be connected to a computer and the VPStudio 4 software for adjusting settings or viewing real-time data. This connection can be made using either a JB5 kit or a USB Mini-B cable. However, when using a USB Mini-B cable, the power ...
    • Standard checklist - flow meter support

      This list of questions is essential to provide the right support. It helps us to be of quicker assistance, as we have a complete picture of the situation. Process: Inner Diameter of the pipe Upstream length Downstream length Average pressure in the ...
    • How to test communication through Modbus?

      Using Modpoll freeware ( VP recommendation) Download it from the links below https://www.vpinstruments.com/service-support/software-firmware or https://www.modbusdriver.com/modpoll.html Unzip the file, open command line (cmd), and change the ...
    • Site visit preparation checklist

      SECURITY CHECK Check safety and personal protection gear. ALWAYS. Eye protection Ear protection Hard Hat Safety Boots Reflective vest Required Permits, Diplomas, Certification for work Equipment list Flowmeters: FlowScope dP with display FlowScope M ...